Masterpact™ NT and NW Universal Power Circuit Breakers
Accessories
57
05/2014
© 2000–2014 Schneider Electric
All Rights Reserved
Test Equipment
Hand-Held Test Kit
The hand held test kit may be used to:
•
Verify trip unit operation, the mechanical operation of the
circuit breaker, and the electrical continuity of the
connection between the trip solenoid and the trip unit.
•
Supply control power to the trip unit for settings via the
keypad when the circuit breaker is open
(Micrologic type A, P or H trip units)
•
Inhibit thermal imaging for primary injection test
(Micrologic type A, P or H trip units)
•
Inhibit ground fault for primary injection test
(Micrologic type A, P or H trip units)
•
Self-restrain zone-selective interlocking (ZSI)
Full-Function Test Kit
The full-function test kit can be used to verify
LSIG functionality.
•
Optional
•
Can be used to check trip unit operation, for example:
— Display of settings
— Operating tests on the electronic component
— Automatic and manual tests on protection functions
(trip curve verification)
— Tests on the zone-selective interlocking
(ZSI) functions
— Inhibit thermal imaging for primary injection testing
— Self-restrain zone-selective interlocking (ZSI)
•
Can also be used to:
— Check mechanical operation of the circuit breaker
— Check the electrical continuity of connection between the trip solenoid and the trip unit
— Print the trip unit and circuit breaker test report when used in conjunction with a PC
FFTK report generator software (cat. no. FFTKRPT-V1-0) is required
Full-Function
Test Kit