Masterpact™ NT and NW Universal Power Circuit Breakers
Selection
163
05/2014
© 2000–2014 Schneider Electric
All Rights Reserved
Table 77: UL 489 Listed, Drawout Automatic Switch
Frame Rating
Model
Number
Withstand Rating
1
1
The withstand rating is the fault current (at rated voltage) that the switch will withstand without
damage when protected by a circuit breaker with an equal continuous current rating.
Instantaneous
Override
240 V 480 V 600 V
800 A
NW08HF 100 kA 100 kA 85 kA 40 kA
NW08HB
2
2
Not available in 4P.
200 kA 150 kA 100 kA 35 kA
1200 A
NW12HF 100 kA 100 kA 85 kA 40 kA
NW12HB
2
200 kA 150 kA 100 kA 35 kA
1600 A
NW16HF 100 kA 100 kA 85 kA 40 kA
NW16HB
2
200 kA 150 kA 100 kA 35 kA
2000 A
NW20HF 100 kA 100 kA 85 kA 40 kA
NW20HB
2
200 kA 150 kA 100 kA 35 kA
2500 A
NW25HF 100 kA 100 kA 85 kA 65 kA
NW25HB
2
200 kA 150 kA 100 kA 65 kA
3000 A
NW30HF 100 kA 100 kA 85 kA 65 kA
NW30HB
2
200 kA 150 kA 100 kA 65 kA
Table 78: IEC 60947-3 Rated, Automatic Switch
Frame Rating
Model
Number
Withstand Rating
1
1
The withstand rating is the fault current (at rated voltage) that the switch will withstand without
damage when protected by a circuit breaker with an equal continuous current rating.
Instantaneous
Override
240 V 440 V 690 V
800 A NW08HF 85 kA 85 kA 85 kA 85 kA
1000 A NW10HF 85 kA 85 kA 85 kA 85 kA
1250 A NW12HF 85 kA 85 kA 85 kA 85 kA
1600 A NW16HF 85 kA 85 kA 85 kA 85 kA
2000 A NW20HF 85 kA 85 kA 85 kA 85 kA
2500 A NW25HF 85 kA 85 kA 85 kA 85 kA
3200 A NW32HF 85 kA 85 kA 85 kA 85 kA
4000 A NW40HF 85 kA 85 kA 85 kA 85 kA