Micrologic 5.0/6.0 A/P/H Trip Units
Characteristic Trip Curve No. 613-5
Short-Time Pickup and I
2
t ON Delay
The time-current curve information is to be used for
application and coordination purposes only.
Curves apply from -30°C to +60°C (-22°F to +140°F)
ambient temperature.
NOTE:
1. There is a thermal-imaging effect that can act to
shorten the long-time delay. The thermal-imaging
effect comes into play if a current above the long-time
delay pickup value exists for a time and then is cleared
by the tripping of a downstream device or the circuit
breaker itself. A subsequent overload will cause the
circuit breaker to trip in a shorter time than normal. The
amount of time delay reduction is inverse to the
amount of time that has elapsed since the previous
overload. Approximately twenty minutes is required
between overloads to completely reset thermal-
imaging.
2. The end of the curve is determined by the interrupting
rating of the circuit breaker.
3. With zone-selective interlocking ON, short-time delay
utilized, and no restraining signal, the maximum
unrestrained short-time delay time band applies
regardless of the setting.
4. Total clearing times shown include the response times
of the trip unit, the circuit breaker opening, and the
extinction of current.
5. For withstand circuit breaker, instantaneous can be
turned OFF. See trip curve 613-7 for instantaneous trip
curve. See trip curve 613-10 for instantaneous
override values.
6. See trip curve 613-4 for long-time pickup and delay trip
curve.
Komentáře k této Příručce