Masterpact™ NT and NW Universal Power Circuit Breakers
Micrologic™ Electronic Trip Systems
28
05/2014
Load Shedding and Reconnection Parameters
Load shedding and reconnection parameters can be set according to the power or the current flowing
through the circuit breaker. Load shedding is carried out by a remote computer via the communication
network or by an M2C or M6C programmable contact.
Indication Option via Programmable Contacts
The M2C (two contacts) and M6C (six contacts) programmable contacts may be used to signal
threshold overruns or status changes. They can be programmed using the keypad on the Micrologic P
and H trip units or remotely using the communication network. These contacts are required to obtain
data from the protective relay functions on Type P and Type H trip units.
Table 26: Micrologic 5.0P and 6.0P Trip Unit Settings
Long-Time
(RMS)
Protection
Current Setting (A)
Tripping Between 1.05
and 1.20 x I
r
I
r
= l
n
x... IEC: 0.40 0.50 0.60 0.70 0.80 0.90 0.95 0.98 1.00
I
r
= l
n
x... UL/ANSI: 0.40 0.45 0.50 0.60 0.63 0.70 0.80 0.90 1.00
Other ranges are available by changing rating plug
Time Delay (s)
Accuracy: 0 to –20%
t
r
at 1.5 x I
r
12.5 25 50 100 200 300 400 500 600
t
r
at 6 x I
r
0.5124812162024
t
r
at 7.2 x I
r
0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
IDMTL Setting
Curve
slope
SIT VIT EIT HV Fuse DT
Thermal Imaging 20 minutes before or after tripping
Short-Time
(RMS)
Protection
Current Setting (A)
Accuracy: ±10%
l
sd
= I
r
x... 1.522.53456810
Time Delay (s)
at 10 x I
r
Settings
I
2
t OFF 0 0.1 0.2 0.3 0.4
I
2
t ON 0.1 0.2 0.3 0.4
t
sd
Min. trip time (ms) 20 80 140 230 350
Max. trip time (ms) 80 140 200 320 500
Instantaneous
Protection
Current Setting (A)
Accuracy: ±10%
I
i
= I
n
x... 23468101215off
Table 27: Micrologic 6.0P Trip Unit Ground-Fault Setting
Ground-Fault Pickup (A)
Accuracy: ±10%
I
g
= l
n
x... A B C D E F G H J
l
n
≤ 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
400 A < l
n
≤ 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
l
n
> 1200 A 500 640 720 800 880 960 1040 1120 1200
Time Delay (s)
at 10 x I
r
Settings
I
2
t OFF 0 0.1 0.2 0.3 0.4
I
2
t ON 0.1 0.2 0.3 0.4
t
g
Minimum trip time (ms) 20 80 140 230 350
Maximum trip time (ms) 80 140 200 320 500
Table 28: Settings for Alarms for Other Protection Functions for Micrologic 5.0P and 6.0P
Trip Units
Threshold Time Delay
Current
Current Imbalance 0.05 to 0.6 x I
max
1 to 40 s
Maximum Current I
max
: I
a
, I
b
, I
c
, I
n
, I
g
0.2 to 1.0 x I
n
15 to 1500 s
Voltage
Voltage Imbalance 0.02 to 0.3 x V
n
1 to 40 s
Minimum Voltage V
min
100 to 725 V (phase total) 0.25 to 0.5 s
Maximum Voltage V
max
100 to 1200 V (between phases) 0.20 to 5.0 s
Power
Maximum Power P
max
5 to 500 kW 0.2 to 20 s
Reverse Power P
r
0.02 to 0.2 x P
n
0.5 to 20 s
Frequency
Minimum Frequency F
min
45 to 65 Hz 0.2 to 5 s
Maximum Frequency F
max
45 to 540 Hz 0.2 to 5 s
Phase Sequence ΔØ ØA-ØB-ØC or ØA-ØC-ØB Instantaneous