MODEL: R7C
http://www.m-system.co.jp/ R7C SPECIFICATIONS ES-7801 Rev.17 Page 13/39
DISCRETE INPUT MODULE, 16 points
MODEL: R7C-DA16
SPECIFICATIONS
Common: Positive or negative common (NPN/PNP) per
16 points
Number of I/O: Input, 16 points
Maximum inputs applicable at once: No limit (at 24 V DC)
I/O status indicator: LED turns on with closed contact.
Isolation: Input to power input to CC-Link or FG
CC-Link: Conforms to Version 1.10
Station type: Remote I/O
Data allocation: 1
Rated input voltage: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current: ≥ 15 V DC (input – COM) / ≥ 3.5 mA
OFF voltage / current: ≤ 5 V DC (input – COM) / ≤ 1 mA
Input current: ≤ 5.5 mA per point at 24 V DC
Input resistance: Approx. 4.4 kΩ
ON delay: ≤ 2.0 msec.
OFF delay: ≤ 2.0 msec.
OPERATING MODE SETTING
(*) Factory setting
Caution ! - SW1-6, 1-7, 1-8 are unused. Be sure to turn off
unused ones.
Output at the loss of communication (SW1-5)
SW1-5 OUTPUT AT THE LOSS OF COMMUNICATION
OFF Reset the output (turned off)
ON Hold the output (*)
(maintains the last data received normally)
Extension (SW1-1, 1-2, 1-3, 1-4)
SW1-1 SW1-2 SW1-3 SW1-4 EXTENSION
ON OFF OFF OFF No extension (*)
ON OFF OFF ON Discrete input, 8 or 16 points
OFF OFF OFF ON Discrete output, 8 or 16 points
TERMINAL ASSIGNMENTS
10
COM
11
X1
12
X3
1
COM
2
X0
3
X2
13
X5
4
X4
14
X7
5
X6
15
X9
6
X8
16
XB
7
XA
17
XD
8
XC
9
XE
18
XF
NO. ID FUNCTION NO. ID FUNCTION
1 COM Common 10 COM Common
2 X0 Input 0 11 X1 Input 1
3 X2 Input 2 12 X3 Input 3
4 X4 Input 4 13 X5 Input 5
5 X6 Input 6 14 X7 Input 7
6 X8 Input 8 15 X9 Input 9
7 XA Input 10 16 XB Input 11
8 XC Input 12 17 XD Input 13
9 XE Input 14 18 XF Input 15